SEISMO Technical Bulletin

Some v3 SEISMO vibration / tilt sensors made between March 2022 and March 2023 can show an incorrect zone resistance at the control panel (CIE). The fix is simple and done on site: reverse the two zone connection wires. No return or modification is needed.

Bulletin20230320
Affectsv3 units only
Made1 Mar 2022 – 19 Mar 2023
RemedyReverse zone wires

Download the bulletin (PDF)

2 pages. Includes photos of the v3 labels and PCB, and wiring diagrams of the normal and abnormal connection.

Affected products

Only v3 products within these serial number ranges are affected:

Product Serial numbers Production dates
SEISMOV3 0000000001 – 0000002091 01/03/2022 – 19/03/2023
SEISMO-ADVANCEV3 0000000001 – 0000002734 01/03/2022 – 19/03/2023
SEISMO-ADVANCE-CV3 0000000001 – 0000000049 01/03/2022 – 19/03/2023
SEISMO-ADVANCE-BKV3 0000000001 – 0000000096 01/03/2022 – 19/03/2023
SEISMO-ADVANCE-GYV3 0000000001 – 0000000004 01/03/2022 – 19/03/2023
SEISMO-ADVANCE-B-CV3 0000000001 – 0000000032 01/03/2022 – 19/03/2023

Products made from 20 March 2023 onwards, with serial numbers above these ranges, are not affected.

How to tell if you have a v3 unit

  1. Label inside the lid: the small product label is marked v3.
  2. Outer packaging: the larger packaging label is also marked v3.
  3. The PCB: v3 boards always have a square potentiometer. Older, unaffected versions have a round one.

If a unit is still sealed in its bag with these labels and was bought before 20 March 2023, assume it is covered by this bulletin.

What happens and why

The control panel shows an abnormal status for the zone the sensor is connected to. The cause is a change to the specification of an onboard ESD protection diode, from bidirectional to unidirectional. If the zone connection is wired with the opposite polarity to the diode, the panel sees a different voltage and so a different zone resistance. Both the alarm and fault output relays are protected by these diodes, so the effect adds up when both outputs are used, as in a Grade 3 TEOL installation.

A standard multimeter will not show the fault. It can be seen with an oscilloscope or at the control panel.

Remedy

Reverse the zone connection wires. This restores normal operation in place, with no need to return or modify the product.

Example from the bulletin, a Pyronix TEOL installation (2k2 / 4k7 / 6k8): wired the wrong way round, the panel reads 3k5 instead of 2k2 secure; with the two zone wires swapped, it reads 2k2 secure. The PDF shows both wiring arrangements.

If reversing the wires does not clear the fault at the panel, please contact us for further help.